A) the direction sign graph of the evacuation indicator should point to the nearest exit or safety exit;

B) set up an evacuation indicator above the exit of the exit or exit exit, and the upper edge of the lower edge of the door should not be greater than the 0.3m;

C) set in the wall of the evacuation signs, signs from center line of the indoor floor should not be greater than 1m (the place is not easy to install can be installed in the upper part), self luminous sign distance should not be greater than 5m, lighting the evacuation indicator spacing should be not greater than 20m (set in the underground buildings, should not be greater than 15m);

D) the evacuation signs on the ground should be set continuously along the evacuation walkway or the main evacuation routes. When the discontinuities are set up, the self luminous spacing between lights should not be greater than 1.5m, and the light evacuation signs should not be greater than 3m.